Skip to main content

 
CXone Expert Clone Site 216

First Run Commisioning

The first-run commissioning ensures your HVAC/refrigeration system is clean, charged correctly, and configured for optimal operation. This article walks through three key phases:

1. Evacuation and Refrigerant Charging

A. Deep Evacuation
  • Connect a vacuum pump and micron gauge to the service port.
  • Pull down to ≤ 500 microns; hold at that level for at least 10 minutes to remove moisture and non-condensables.
  • Close valves, isolate the vacuum pump, and monitor for pressure rise—any rise indicates moisture ingress or leak.
B. Refrigerant Charging by Weight
  • Attach refrigerant cylinder to manifold gauge set.
  • Weigh in the exact charge specified by the manufacturer on the unit nameplate.
  • Allow refrigerant to flow as liquid into the liquid line; switch to vapor injection on suction side if required.
C. Fine-Tuning by Superheat/Subcooling
  • Measure suction-line superheat at the evaporator outlet.
  • Adjust charge to achieve target superheat (e.g., 8–12 °F/4–6 °C) or subcooling (e.g., 8–12 °F/4–6 °C) per the spec sheet.
  • Document readings for future performance benchmarking.

2. Startup Sequences and Control-Panel Configuration

A. Power-Up and Self-Test
  • Restore power at the fused disconnect; observe initial control-board self-test flashes or codes.
  • Clear any stored fault codes before proceeding.
B. Control Parameters & Setpoints
  • Enter correct system type (cooling, heating, heat-pump) into the panel menu.
  • Program thermostat deadbands, staging parameters, and minimum run times as per design.
  • Configure safety limits—high/low pressure cut-outs, freeze-stat protections, and float switch actions.
C. Sensor Calibration
  • Verify thermostat and pressure sensor readings against a calibrated handheld meter.
  • Adjust offset or span settings in the controller to match actual values within ± 2 °F (± 1 °C) or ± 1 psi.

3. Verifying Performance (Temperatures, Pressures, Airflow)

A. Temperature Measurements
  • Record entering and leaving air temperatures across the evaporator; target ΔT of 15–20 °F (8–11 °C) for A/C.
  • Confirm condenser discharge air is within expected range (typically 20–30 °F/10–15 °C above ambient).
B. Pressure Readings
  • Verify suction and head pressures on the manifold gauge; compare to manufacturer’s pressure–temperature chart.
  • Ensure head pressure does not exceed design limits under current ambient conditions.
C. Airflow & Electrical Load
  • Measure static pressure across filters and coils; confirm airflow (CFM) meets design (e.g., 350–450 CFM/ton).
  • Check current draw on compressor and fans against FLA; ensure ≤ 110% of nameplate FLA.
  • Was this article helpful?